7 Troubleshooting
38 / 44 BAL_K21_EN_3V3_BLA_121-006423019
61 SSK aktive STA/DFA: The signal on the key-operated contact is permanently active.
– Check the SSK switch and wiring/connections.
– The response time for the error can be configured or the error message
can be disabled (see Parameter → Miscellaneous → Alarm display →
Time activation).
62 BDE no priority W STA: The requested operating mode cannot currently be set because an op-
erating mode with a higher priority has been selected on one of the mechan-
ical controls (BDE-M, SURV, SURA, etc.).
DFA: The requested operating mode cannot currently be set because an op-
erating mode with a higher priority has been selected on one of the mechan-
ical controls (BDE-M).
For instance, if operating mode Locked has been set on the BDE-M, one
cannot change to Automatic with the BDE-D.
97 Maintenance time ex-
ceeded
W
R
The configured maintenance cycle has already been exceeded for a certain
time (>105%).
– Inform our after-sales service centre urgently and have maintenance car-
ried out.
– By acknowledging the warning message, the alarm is reset for 13 days.
98 Maintenance due W
R
95% of the configured maintenance cycle has been reached.
– Inform our after-sales service centre and have maintenance carried out
soon.
– The warning can be acknowledged. It will be displayed again when 100%
of the maintenance cycle has been reached.
101 Learning sensor W STA: The special door run for learning the sensors is being carried out.
– Trigger several door openings until the message disappears.
111 Fire alarm External fire alarm / smoke removal contact is activated.
– If false alarm, check contacts and connections.
112 Batt. not charged com-
plete
W STA: The battery is not completely charged.
– Connect it to mains voltage.
– The message disappears as soon as the battery is fully charged.
304 Sliding door open Sliding door is open.
– Wait for sliding door to automatically close or push together manually.
305 VRR error
radial wing
Error when locking the radial protective sliding wing.
– Press the “Locked” operating mode on the BDE-D again.
306 VRR error rotor Error when locking the rotation unit.
– Press the “Locked” operating mode on the BDE-D again.
345 OP-VLS1 > 60s active Vertical forward sensor is activated for longer than 60 sec.
– Check that no objects are activating the vertical forward sensor.
346 OP-VLS2 > 60s active Vertical forward sensor is activated for longer than 60 sec.
– Check that no objects are activating the vertical forward sensor.
353 OP-VSSA > 60s active Vertical forward sensor is activated for longer than 60 sec.
– Check that no objects are activating the vertical forward sensor.
354 OP-VSSI > 60s active Vertical forward sensor is activated for longer than 60 sec.
– Check that no objects are activating the interior vertical sensor.