9. OUTPUT MODULES [Optional] (For All Output Channels):
Relay:
Type:Form-C(Form-Awith somemodels.SeeOrderingInformation)
Rating: 5 Amps @ 120/240 VAC or 28 VDC (resistive load), 1/8 HP @
120 VAC (inductive load)
Life Expectancy: 100,000 cyclesat maximumload rating. (Decreasing
load and/or increasing cycle time, increases life expectancy).
Logic/SSR Drive: Can drive multiple SSR Power Units.
Type: Non-isolated switched DC, 1 2 VDC typical
Drive:45mAmaximum
Triac:
Type: Isolated, Zero Crossing Detection
Rating:
Voltage: 120/240 VAC
Max. Load Current: 1 Amp @ 35°C
0.75 Amp @ 50°C
Min. Load Current:10mAmax.
Offstate Leakage Current: 7 mA max. @ 60 H z
Operating Frequency:20to400Hz
Protection: Internal Transient Snubber, Fused
10. MAIN CONTROL OUTPUT (Heating or Cooling):
Control: PID or ON/OFF
Output: Time proportioning or linear DC
Hardware: Plug-in, replaceable output modules
Cycle time: Programmable
Auto-tune: When selected, sets proportional band, integral time,
and derivative time values.
Probe Break Action: Programmable
11. COOLING OUTPUT (Optional):
Control: PID or ON/OFF
Output: Time proportioning or linear DC
Hardware: Plug-in, replaceable output modules
Cycle time: Programmable
Proportional Gain Adjust: Programmable
Heat/Cool Deadband Overlap: Programmable
12. LINEAR DC OUTPUT (Optional): With digital scale and offs et,
programmable deadband and update time
4to20mA:
Resolution: 1 part in 3500 typ.
Accuracy: ± (0.1% of reading + 25 mA)
Compliance:10V(500W max. loop impedance)
0 to 10 VDC:
Resolution: 1 part in 3500 typ.
Accuracy: ± (0.1% of reading + 35 mV)
Min. Load Resistance:10K
W (1 mA max.)
Source: % output power, setpoint, d eviation, or temperature
(Available for heat or cool, but not both.)
13. HEATER CURRENT MONITOR (Optional):
Type: Single phase, full wave monitoring of load currents controlled by
main output (OP1)
Input: 100 mA AC output from current transformer RLC part number
#CT005001 or any current transformer with 100 mA AC output
Display Scale Range: 1.0 to 999.9 amperes or 100.0%
Input resistance:5W
Accuracy:1%offullscale± 1 LSD (10 to 100% of range)
Frequency: 50 - 400 Hz
Alarm mode: Dual acting; heater element fail detect and control device
fail detect
Overload: 200 mA (steady state)
Minimum o utput “on” time for Heater break alarm detect: 400 msec
14. MOTORIZED VALVE POSITIONER (Optional):
Two Outputs: Valve open and valve close or Linear DC (optional)
Hardware: Plug-in, replaceable output modules
Three Inputs: Slidewire feedback, signal fail detect
(Isolated from main input)
Slidewire resistance: 100 to 100 KW
Slidewire exciting voltage: 0.9 VDC
Slidewire fail action: programmable
Control mode: Position mode (with slidewire) and
Velocity mode (w/o slidewire)
Control deadband: 0 .1% to 25.0% (position mode)
0.1 to 25.0 seconds (velocity mode)
Update time: 1 to 250 seconds
Motortime(open,close): 1 to 9999 seconds
Position limits: Adjustable 0.0 to 100.0% of valve stroke