MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
198 8540780 • 10/07/2020 • Rev.38
English
PASSING MAKE CONTACT
In the PASSING MAKE CONTACT operator the output
follows the signal on the input. However, if this is 1
(TRUE) for longer than the set time, the output
changes to 0 (FALSE). When there is an input falling
edge, the timer is cleared.
Parameters
Time: The delay can be set to between 10 ms and 1098,3 s.
Scale: The user can choose two different scales for the time T to be set.
10 ms...60 s, step 10 ms
60,1 s...1098,3 s, step 100 ms
Retriggerable: If selected the time is not reset when there is an input falling edge.
The output stays 1 (TRUE) for all the selected time. When there is a new input rising edge,
the timer restart again.
Rising edge
T = set time
Rising edge
T = set time