EasyManua.ls Logo

Reer MOSAIC M1 - Restart_Fbk

Reer MOSAIC M1
239 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
8540780 • 10/07/2020 • Rev.38 37
English
RESTART_FBK
The RESTART_FBK signal input allows the MOSAIC to verify an EDM (External Device
Monitoring) feedback signal (series of contacts) from the external contactors, and to
monitor Manual/Automatic operation (See the list of possible connections in Table 24).
If the application requires it, the response time of the external contactors must be verified by
an additional device.
The RESTART command must be installed outside the danger area in a position where the
danger area and the entire work area concerned are clearly visible.
It must not be possible to reach the control from inside the danger area.
MODE OF
OPERATION
EDM
RESTART_FBK
AUTOMATIC
With K1_K2
control
K2
K1
24V
ext_Restart_fbk
Without
K1_K2
control
24V
ext_Restart_fbk
MANUAL
With K1_K2
control
K2
K1
24V
ext_Restart_fbk
Without
K1_K2
control
24V
ext_Restart_fbk
Table 24

Table of Contents

Other manuals for Reer MOSAIC M1

Related product manuals