MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
8540780 • 10/07/2020 • Rev.38 77
English
MI12T8 (Figure 39)
LED
MEANING
RUN
IN FAIL
EXT FAIL
SEL0/1
IN1÷12
REMEDY
GREEN
RED
RED
ORANGE
YELLOW
Internal fault
OFF
2 or 3 flashes
OFF
Shows the physical
address of the unit
OFF
Return the unit to ReeR to be repaired
Compatibility error
OFF
5
flashes
OFF
5
flashes
Firmware version not compatible with M1,
return to ReeR for FW upgrade.
Error in communication with
master
OFF
5
flashes
OFF
OFF
Restart the system
If the problem persists, return the unit to
ReeR to be repaired
Error on other
slave or M1
OFF
ON
OFF
OFF
Restart the system
Check which unit is in FAIL mode
Same type of slave with
same address detected
OFF
5
flashes
5
flashes
OFF
Change the unit's address (see NODE SEL)
Node detection circuit error
OFF
3
flashes
OFF
3
flashes
OFF
Return the unit to ReeR to be repaired
Table 69 - Troubleshooting MI12T8
Figure 39 - MI12T8