MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
8540780 • 10/07/2020 • Rev.38 85
English
MV0, MV1, MV2 (Figure 47)
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL0/1
ENC*
PROX
SH
GREEN
RED
RED
ORANGE
YELLOW
YELLOW
YELLOW
Internal fault
OFF
2 or 3
flashes
OFF
Shows the
physical
address
of the unit
OFF
OFF
OFF
Return the unit to
ReeR to be repaired
Compatibility error
OFF
5
flashes
OFF
5
flashes
5
flashes
5
flashes
Firmware version not
compatible with M1,
return to ReeR for FW
upgrade.
Encoder INTERNAL
error
OFF
3
flashes
OFF
3
flashes
OFF
OFF
Change the encoder
Return the unit to
ReeR to be repaired
Proximity
INTERNAL error
3
flashes
OFF
3
flashes
Change the proximity
Return the unit to
ReeR to be repaired
Error on node
detection circuit
OFF
3
flashes
OFF
3
flashes
OFF
OFF
OFF
Return the unit to
ReeR to be repaired
Same type of slave
with same address
detected
OFF
5
flashes
5
flashes
Shows the
physical
address
of the unit
OFF
OFF
OFF
Change the unit's
address
(see NODE SEL)
Encoder not
connected but
requested from the
configuration
OFF
OFF
continuous
flashes
continuous
flashes
OFF
OFF
Verify encoder
connection and power
supply
Verify input frequency
(in range)
Proximity not
connected but
requested from the
configuration
OFF
OFF
continuous
flashes
OFF
continuous
flashes
OFF
Verify proximity
connection
Verify input frequency
(in range)
Table 77 - Troubleshooting MV1/MV2