MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
8540780 • 10/07/2020 • Rev.38 41
English
OSSD (MO4LHCS8)
MO4LHCS8 provides 4 High Current Safety Outputs single channel (2A max per channel).
These outputs are short circuit protected, cross circuit monitored and supply:
In the ON condition: (Uv-0,6V) ÷ Uv (24VDC ± 20%)
In the OFF condition: 0V ÷ 2V r.m.s.
The maximum load of 2A@24V corresponds to a minimum resistive load of 12.
The maximum capacitive load is 0.82F. The maximum inductive load is 2.4 mH.
Different output configurations (configurable with MSD configuration software) can be set:
Four single channels (1 Safety Output per channel with its relative feedback input).
Two dual channels (2 Safety Outputs per channel with their relative feedback input).
1 dual channel and 2 single channels.
Using single channels OSSD, to maintain Safety Integrity Level (SIL) "3" requirements the OSSD
outputs must be independent.
Common cause failures between OSSD outputs must be excluded by observing an appropriate
cable installation (i.e. separate cable paths).
Using MO4LHCS8 with sum output current > 5 A, then separate adjacent modules by
interposing a MSC connector.