MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
8540780 • 10/07/2020 • Rev.38 75
English
MI8O4 (Figure 37)
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL0/1
IN1÷8
OSSD1/4
STATUS1/4
GREEN
RED
RED
ORANGE
YELLOW
RED/GREEN/YELLOW
YELLOW
Internal fault
OFF
2 or 3
flashes
OFF
Shows the
physical
address of the
unit
OFF
Red
OFF
Return the unit to ReeR
to be repaired
Compatibility error
OFF
5
flashes
OFF
5 flashes
5
flashes
5
flashes
Firmware version not
compatible with M1,
return to ReeR for FW
upgrade.
OSSD output error
OFF
4
flashes
OFF
OFF
4 flashes
(only the LED corresponding
to the output in FAIL mode)
OFF
Check OSSD1/2
connections
If the problem persists,
return the unit to ReeR
to be repaired
Error in
communication with
master
OFF
5
flashes
OFF
OFF
OFF
OFF
Restart the system
If the problem persists,
return the MI8O4 to
ReeR to be repaired
Error on other
slave or M1
OFF
ON
OFF
OFF
OFF
OFF
Restart the system
Check which unit is in
FAIL mode
Same type of slave
with same address
detected
OFF
5
flashes
5
flashes
OFF
OFF
OFF
Change the unit's
address (see NODE
SEL)
Overload on OSSD /
OSSD load connected
to 24V
ON
OFF
ON
Shows the
physical
address of the
unit
Inputs
State
Red blinking (only LED
corresponding to the
relative output)
OUTPUT
state
Verify OSSD connections
Short circuit or
overload detected on
status output
ON
OFF
ON
Shows the
physical
address of the
unit
Inputs
State
OUTPUT
state
blinking
Verify output status
connections
Table 67 - Troubleshooting MI8O4