— English Variomat 1 — 06.07.2016 – Rev. B
-selected time for a make-up cycle. Upon expiry of this set time, the system interrupts
-up and returns the "Make-up time" fault message.
Max. make-up time
010 min.
If the set number of make
-up cycles is exceeded within two hours, the system interrupts
-up and returns the "Make-up cycles" fault message.
Max. make-up cycl.
003 / 2 h
FQIRA+ contact water meter is installed, see chapter 4.6 "Optional equipment and
accessories" on page 13 .
This is the prerequisite for the make-up quantity monitoring and the operation of a
softening system.
With water meter
YES
A contact water meter is not installed (standard model).
Only displayed if "YES" has been set in the "With water meter" menu option.
Use "OK" to delete the counter.
– Press "YES" to reset the value displayed to "0".
– Press "No" to retain the displayed value.
Make-up quantity
000020 l
This value is only displayed if "YES" has been set in the "With water meter" menu option.
When the set quantity is exceeded, the system interrupts the make-up process and
returns the error message "Max. make-up quantity exceeded".
Max. make-up qty.
000100 l
This value is only displayed if "YES" has been set in the "With water meter" menu option.
With softening
YES
The system offers more queries regarding the softening process.
The system does not offer more queries regarding the softening process.
This value is only displayed if "YES" has been set in the "With softening" menu option.
Lock make-up?
YES
The system stops the make-up process when the set soft water capacity is exceeded.
The system does not stop the make-up process. The system displays the "Softening"
message.
This value is only displayed if "YES" has been set in the "With softening" menu option.
Hardness reduction is calculated from the difference of the overall water hardness
GH
actual
and the target water hardness GH
target
.
– Hardness reduction = GH
actual
-GH
target
l °dH
Enter the value in the controller. Consult the manufacturer information for
third-party
Hardness reduction
10 °dH