Authorized service centers can modify all UPS configurations through configuration software (“Configurator” of
"UComGP" program) as below defined:
Selects one of five different
operating modes
On Line
Eco
Smart Active
Stand-By Off
Frequency Converter
Selects the rated output
voltage
(Phase - Neutral)
220 ÷ 240 1 V step
200 V with power downgrading
208 V with power downgrading
Selects the rated output
frequency
Waiting time for automatic
power-on after the return of
mains voltage
Disabled
Delay: 1 - 255 @1 sec step
Automatic UPS power-off in
battery operation mode if the
charge is lower than 5%
Selects the audible alarm
operating mode
Normal
Reduced: does not sound due to the
momentary intervention of the bypass
Selects the auxiliary socket
operating mode
Always connected
Disconnection after n seconds of battery
operation
Disconnection after n seconds from the
battery low pre-alarm signal
(see software configuration manual)
Programmed UPS switching
ON-OFF
(daily)
Timer ON (hh:mm)
Timer OFF (hh:mm)
Maximum battery operation
time
Disabled (complete battery discharge)
1 - 65534 @1 sec step
Selects the user overload
limit
Disabled
0 - 103 @1 % step
Power walk-in
start delay
Adjustable delay for the
power walk-in start up
Disable (0 sec set up)
Enable 1 ÷120 @1 sec step
Gradual Input current ramp
absorption following mains
return
Disable (0 sec set up)
Enable 1 ÷ 125 @1 sec step