SPTMSTD2T16EREN
21
>9.4 CONFIGURATION SOFTWARE
User can modify some of the UPS configurations from the operating mimic panel; here below the list of adjustable
functions:
FUNCTION
DESCRIPTION
DEFAULT
POSSIBLE CONFIGURATIONS
Language*
Selects mimic panel
language
English
English
Italian
German
French
Spanish
Polish
Russian
Chinese
Output voltage
Selects the rated output
voltage
(Phase - Neutral)
230 V
220 V
230 V
240 V
Buzzer
Selects the audible alarm
operating mode
Reduced
Normal
Reduced: does not sound due to the
momentary intervention of the bypass
Operating mode**
Selects one of four
different operating modes
ON LINE
On Line
Eco
Smart Active
Stand-By Off
Battery low**
Estimated autonomy time
remaining for “battery
low” warning
3 min.
1 ÷ 7 @1 min step
Date and time**
UPS internal watch setup
* Pressing the F1 and F4 keys at the same time for t > 2 sec will automatically reset English as default language.
** This function might be locked by configuration software.