Electrical Specifications
Efficiency AC/AC (On line) – (%)
UPS on line mode without load [W]
UPS stand-by without load [W]
Efficiency with UPS in ECO mode
Audible noise at 1 mt (according to EN
62040-3) -[dBA +/- 2 dBA]
Max. relative humidity during operation
Max. installation altitude
1000 m at nominal power
(-1% power for each 100 m above 1000 m)
Max 4000 m
Power dissipated with resistive nominal
load (pf=0,9) and battery charged*
0,63 kW
540 kcal/h
2150 B.T.U./h
0,75 kW
645 kcal/h
2560 B.T.U./h
0,86 kW
740 kcal/h
2940 B.T.U./h
1,15 kW
990 kcal/h
3930 B.T.U./h
Power dissipated with resistive nominal
load (pf 0,9) and with battery under
recharge*
0,74 kW
637 kcal/h
2525 B.T.U./h
0,86 kW
740 kcal/h
2940 B.T.U./h
0,98 kW
843 kcal/h
3343 B.T.U./h
1,27 kW
1092 kcal/h
4333 B.T.U./h
Max current leaked to earth**
(4)
Data refer to typical load (75% kVA and pf 0,66):
* 3,97 B.T.U. = 1 kcal
** The leakage current of the load on the UPS adds to the protective earth conductor