Apparent Power
Power Factor / Phase Angle
+3°
Active energy
Reactive energy
Class 2 as per IEC 62053-23 & 61557 - 12
Apparent energy
Class 1 as per IEC 61557 - 12
THD (V/I) w.r.t. Fundamental
+ 5 % (upto 31st harmonics)
Display
Approx. 1 sec.
3 Line 5 Digit & 1 Line 9 Digit row LCD Display with backlit
Response time to step input
Controls
4 push buttons
User Interface
Standards
+ 0.5% (0.2% optional) of nominal value
Class 0.5S (0.2S optional) as per IEC 62053-22
Class 0.5 (Class 0.2 for 5A In and Class 0.5
for 1A In optional) as per IEC61557 - 12
Voltage + 0.5% (0.2% optional) of nominal value
Current
Frequency
+ 0.1 % of mid frequency
Active power
+ 0.5% (0.2% optional) of nominal value
+ 0.5% (0.2% optional) of nominal value
Reactive power
+ 1.0% of nominal value
Accuracy
Individual Harmonics
+ 5 % (upto 31st harmonics)
IEC 61010-1-2010,
permanently connected use
Safety
IEC 61326 - 1, Table 2
Electromagnetic Compatibility
Immunity
IEC 61000-4-2,-3,-4,-5,-6,-8,-11
Automatic / Manual (Programmable)
Scrolling
CISPR 11
Emission
Pollution degree
2
III
Installation Category 300V CAT / 600V CAT
II
IEC 60529
IP for water & dust
99