3.2.1.5 Current Transformer Secondary Value
This screen is used to set the secondary value for Current Transformer.
Secondary value “5” for 5A or “1” for 1A can be selected.
Pressing the “ ” key accepts the present value and advances to the
“System Frequency” menu (see Section 3.2.1.6).
Similarly, pressing the “ ” key accepts the present value and advances to
the “Current Transformer Primary Value” screen (see Section 3.2.1.4).
Pressing the “ ” key advances to the “CT Secondary Value Edit” mode
and keys “ ” and “ ” scroll the value through the options available.
3.2.1.6 System Frequency
Pressing the “ ” key sets the option selected and advances to “Pls Wait” screen followed by “Current
Transformer Secondary Value” screen (see Section 3.2.1.5).
NOTE: Default value is set to ‘5’ i.e. 5A.
This screen is used to set the frequency of the input. The Unit of displayed
values is Hz.
Pressing the “ ” key enables editing and pressing the “ ” or “ ” key
scrolls through the following Options: 50,60 Hz.
Once the desired option has been selected, pressing “ ” key confirms
the selection and advances to the “System Frequency” menu (see Section
3.2.1.6).
Pressing the “ ” key advances to “Demand Integration Time” screen (see Section 3.2.1.7) and pressing the
“ ” key advances to “Current Transformer Secondary Value” screen (see Section 3.2.1.5).
NOTE : (1) The applied frequency and the entered frequency value should be same.
(2) Default value is set to ‘50’ Hz.