Pressing “ ” key prompts for first digit.
Press the “ ” and “ ” key to scroll the value of the first digit.
Press the “ ” key to advance to next digit.
The second digit prompts. Press “ ” and “ ” keys to scroll through 0
and 9 and “ ” key to set the digit and advance to the third digit. The third
digit prompts. Press “ ” and “ ” keys to scroll through 0 and 9.
Press “ ” to confirm the value and advance to “Hysteresis” screen (see
Section 3.2.5.1.1.2.4). Refer Section 5.2 for further details.
3.2.5.1.1.2.4 Hysteresis
This screen applies to the Hysteresis selection. This screen allows the user
to set Hysteresis for relay output.
The allowable range is 0.5% to 50.0 % of Trip point.
Pressing the “ ” key accepts the present value and advances to the
“Logic Operation Selection” screen (see Section 3.2.5.1.1.2.6) and
pressing the“ ” key accepts the present value and advances to the “Trip
Point” screen (see Section 3.2.5.1.1.2.3).
XXXXXXXX
XXXXXXXX
3.2.5.1.1.2.3 Trip Point
This screen allows the user to set Trip point for selected limit relay.
The allowable range is 10% to 120% for High Alarm, 10% to 100% for
Low Alarm (refer TABLE 3).
Pressing the “ ” key accepts the present value and advances to the
“Hysteresis” screen (see section 3.2.5.1.1.2.4) and pressing the “ ” key
accepts the present value and advances to the “Alarm Configuration”
screen (see Section 3.2.5.1.1.2.2).
This screen applies to Trip point selection for parameters other than 37 to 41 & 200 to 232 (Refer TABLE 3)
selected in Section 3.2.5.1.1.2.1.
Pressing “ ” key prompts the first decimal. Press the “ ” and “ ” keys to scroll the decimal position.
Again, pressing the “ ” key prompts the first digit, and pressing “ ” & “ ” key scroll through the value of the
first digit. Pressing “ ” key prompts the second digit. Similarly, enter third and fourth digits also.
Note: Default value is set to ‘10.00’ %.
XXXXXXXX
Note: Default value is set to ‘00.5’ %.
51