Installation site requirements
© robatherm 13
Footprint requirements
AHUs have the following footprint requirements:
Fig. 2: AHU footprint requirements
A - revision area; B - unit width; C 875 mm; D 500 mm
• Leave 875 mm (C) free for connections and escape routes on all sides of the AHU.
To replace components (e.g., coil, filter wall I - O, fan) on the operating side, leave one unit
width (B) free as a revision area (A).
• Leave 500 mm (D) free above the AHU as a revision area (A).
Steam generator for electro steam humidifier
For steam generators for electro steam humidifiers, observe the minimum wall clearance according to
the manufacturer.