154 Publication IASIMP-QS003B-EN-P - October 2009
Chapter 11 Create a PowerFlex 70 Application
5. Change ClearFault tag
back to 0 and press Enter.
6. Verify that the
I.DriveStatus_Ready tag
value is 1, indicating that
the drive is ready.
7. Change the
O.CommandedFreq tag
to 15000 engineering
units and press Enter.
This is about 59.5 Hz.
8. Change the Start tag to 1
and press Enter.
The display on the drive
registers the speed
increase in Hz until the
value entered at the
reference tag is reached.
9. Change the Start tag back
to 0.
WARNING
If there is a motor attached to your drive,
completing the next step will cause it to turn.
EU
Hz
---------
32767
130
--------------=