154 Publication IASIMP-QS003B-EN-P - October 2009 
Chapter  11        Create a PowerFlex 70 Application
5. Change ClearFault tag 
back to 0 and press Enter.
6. Verify that the 
I.DriveStatus_Ready tag 
value is 1, indicating that 
the drive is ready.
7. Change the 
O.CommandedFreq tag 
to 15000 engineering 
units and press Enter.
This is about 59.5 Hz.
8. Change the Start tag to 1 
and press Enter.
The display on the drive 
registers the speed 
increase in Hz until the 
value entered at the 
reference tag is reached. 
9. Change the Start tag back 
to 0.
If there is a motor attached to your drive, 
completing the next step will cause it to turn.
EU
Hz
---------
32767
130
--------------=