158 Publication IASIMP-QS003B-EN-P - October 2009 
Chapter  11        Create a PowerFlex 70 Application
8. Change the O.Start tag to 
1.
The display on the drive 
registers the speed 
increase in Hz until the 
value at the reference tag 
is reached.
9. Change the O.Start tag 
back to 0.
10. Change the O.Stop tag to 
1. 
The display on the drive 
shows a speed decrease 
until the drive reaches 
0.00 Hz.
11. Change the O.Stop tag 
back to 0.
12. Go Offline and save.
If there is a motor attached to your drive, completing the next step will cause it to turn.