128 Rockwell Automation Publication 5094-UM001E-EN-P - April 2020
Appendix A Troubleshoot Your Module
Tab le 25 describes the I/O Status indicators on FLEX 5000 input modules.
STATUS
POWER
FLEX 5000
TM
I/O
DIGITAL 8 INPUT AC
5094-IM8
TB3AC
0123 4567
42
Input Point 0 (I00)
Input Point 1 (I01)
Input Point 2 (I02)
Input Point 3 (I03)
Input Point 4 (I04)
Input Point 5 (I05)
Input Point 6 (I06)
Input Point 7 (I07)
SA power status indicator
I/O status indicators
5094-IM8, 5094-IM8XT
Module status indicator
Table 25 - I/O Status Indicators - FLEX 5000 Input Modules
Indicator State Description Recommended Action
Off One of the following:
The input point is Off.
There is no backplane power.
One of the following:
Confirm that the input point is
configured properly.
Confirm that there is backplane power
supplied through the FLEX 5000
EtherNet/IP adapter.
Steady yellow The input point is operating normally. None
Flashing red A Field Power Loss condition exists. Locate and correct the cause of field power
loss condition.