For information on electrical noise reduction, refer to the System Design for
Control of Electrical Noise Reference Manual, publication GMC-RM001
.
To meet CE requirements, these requirements apply:
• Install an AC line filter (catalog number 2090-XXLF-TCxxx) as close to
the drive as possible.
• Use 2090 series motor power cables and terminate the cable shields to the
drive or subpanel.
• Use 2090 series motor feedback cables and properly terminate the
feedback cable shield. Drive-to-motor feedback cables must not exceed
30 m (98.4 ft). Drive-to-motor power cables must not exceed 30 m
(98.4 ft).
• Install the Kinetix 3 system inside an enclosure. Run input power wiring in
conduit (grounded to the enclosure) outside of the enclosure. Separate
signal and power cables.
• Segregate input power wiring and motor power cables from control wiring
and motor feedback cables. Use shielded cable for power wiring and
provide a grounded 360° clamp termination.
Refer to Appendix A
on page 123 for interconnect diagrams, including input
power wiring and drive/motor interconnect diagrams.