Step 5: Enter Motor Data
Enter Motor Poles
If the number of motor poles is not on the motor nameplate, contact the motor manufacturer and confirm the number of
motor poles. The number of motor poles is ALWAYS an even integer multiple of 2.
Use this table to help determine the number of poles. The motor NP RPM is always less than the Sync RPM by the
amount of motor slip RPM. If the motor NP Hertz is not 50 Hz or 60 Hz, or if the motor has a low NP RPM, contact
the motor manufacturer and confirm the number of poles.
1. Navigate to parameter 10:407 [Motor Poles]. Press the EDIT soft key.
2. Edit the number of motor poles to match the data collected Ta b le 1 on pa ge 8
.
3. Press the ENTER soft key.
No. Poles Sync RPM
NP Hertz = 60 Hz
Sync RPM
NP Hertz = 50 Hz
2 3600 3000
4 1800 1500
6 1200 1000
8900750
10 720 600
12 600 500

Table of Contents

Other manuals for Rockwell Automation Allen-Bradley PowerFlex 750 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley PowerFlex 750 Series and is the answer not in the manual?

Rockwell Automation Allen-Bradley PowerFlex 750 Series Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley PowerFlex 750 Series
CategoryDC Drives
LanguageEnglish

Related product manuals