89Publication 2100-IN012C-EN-P - April 2009 89
Chapter
8
Energizing the Equipment
Energize the Equipment
1. Review any additional instructions supplied for the proper
operation of special units such as variable frequency drives and
soft starters with appropriate and qualified personnel.
2. Check that there is no load on the MCC when it is energized.
3. De-energize all main and unit disconnect devices.
4. Check to see if any associated remote devices are de-energized.
5. Energize the MCC remote power source.
ATTENTION
This procedure is provided as a general guidance for energizing
a newly installed CENTERLINE MCC and should be used after
the Final Check procedure has been completed. See Final
Check List Before Energizing for more information.
ATTENTION
Energizing a MCC for the first time is potentially dangerous.
Serious damage and or personal injury can result when power
is applied. Therefore, only qualified personnel should energize
the equipment.
ATTENTION
When working on or near energized electrical equipment,
follow established electrical safety-related work practices.
Refer to NFPA 70E Standard for Electrical Safety in the
Workplace.