EasyManua.ls Logo

RTA 490NBX - Setting up ASCII to PLC Communication; Defining an End Case for the ASCII Message

RTA 490NBX
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Setting up ASCII to PLC Communication
1) Click the ASCII Configuration button under the CONFIGURATION section.
2) Check the Enable Communication checkbox to modify the fields below.
3) Data Type: Select the Data Type for the Tag / File Name that you defined in the PLC.
a. If PLC Type configured is I/O Scanner, then this field will be grayed out.
4) Enter the Tag / File name you want the gateway to move the ASCII message to.
a. The Tag / File must be defined in the PLC and must match exactly.
b. The Tag Name must be defined within the Controller Scope of the PLC for Read/Write
Access.
Defining an End Case for the ASCII Message
5) To define an ASCII message, you must select one or more of the following end cases: Character
Count, Timer, or Delimiters.
a. Character Count: Enter the max number of characters that the device could output.
Example: If your device sends a four digit temperature, set the length to 4.
i. If using an INT Data Type, this is also the dimension size/2 + 1 of the Tag / File.
ii. If using a SINT Data Type, this is also the dimension size + 2 of the Tag / File.
Real Time Automation, Inc. 16 1-800-249-1612

Related product manuals