EasyManua.ls Logo

RTA 490NBX - Setting up PLC to ASCII Communication

RTA 490NBX
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Setting up PLC to ASCII Communication
1) Click the ASCII Configuration button under the CONFIGURATION section.
2) Check the Enable Communication checkbox to modify the fields below.
3) Data Type: Select the Data Type for the Tag / File Name that you defined in the PLC.
a. If PLC Type configured is I/O Scanner, then this field is not used.
4) Enter the Tag / File name that you want the gateway to monitor for messages.
a. The Tag / File must be defined in the PLC and must match exactly.
b. The Tag Name must be defined within the Controller Scope of the PLC for Read/Write
Access.
5) Character Count: Enter the maximum number of characters that the gateway can send to the
ASCII device.
a. If using an INT Data Type, this is also the dimension size/2 + 1 of the Tag / File.
b. If using a SINT Data Type, this is also the dimension size + 2 of the Tag / File
c. For Controllers using RSLogix5000, the range for each data type is:
i. STRING/INT/SINT: 0-4096 characters.
ii. STRING– If using more than 82 characters, a User Defined Data Type must be
created within the PLC and used. Refer to Appendix C
for instructions.
d. For Controllers using RSLogix500, the range for each data type is:
Real Time Automation, Inc. 18 1-800-249-1612

Related product manuals