EasyManua.ls Logo

RTA 490NBX - Main Page Does Not Launch

RTA 490NBX
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Main Page Does Not Launch
If the Main Page does not launch please verify the following:
1) Check that the PC is set for a valid IP Address
a. Open a MS-DOS Command Prompt
b. Type “ipconfig” and press enter
c. Note the PC’s IP Address, Subnet, and Default Gateway
i. An invalid IP Address would be: 169.254.x.x
2) The gateway must be on the same Network/Subnet as the PC
Once you have both devices on the same network, you should be able to ping the 490NBX using a MS-
DOS Command Prompt.
If you are able to successfully ping your gateway, open a browser and try to view the main page of the
gateway by entering the IP Address of the gateway as the URL.
Real Time Automation, Inc. 8 1-800-249-1612

Related product manuals