7-4 EB 3018 EN
Operation
With Type5827-A… Electric Actuator
1)
1. Retract the actuator stem by applying a
corresponding control signal from the
control device.
2. Loosen the locking screw (2.6) and turn
the set point adjuster (2.3) clockwise ()
as far as it will go to close the restriction
(2.7).
3. Determine the turns required to achieve
the desired ow rate from the adjustment
diagrams (see Table 7-1).
4. Based on a closed restriction, turn the set
point adjuster counterclockwise () to
adjust the ow rate set point.
5. Check the ow rate at the heat meter and
correct it, if necessary.
6. Once the ow rate is set as required,
lock the setting with the locking screw
(2.6).
7. Close a possibly open bypass valve
again.
8. Lead-seal the setting, if necessary.
Once the magnet has been released, the
spring mechanism pushes the actuator stem
back to the fail-safe position.
Note
7.2.2 DN65 to 100
Type5827-N3
2)
or Type3374 Electric
Actuator
Î Adjustment without actuator · See
Fig.7-1
1. Thread the lock nut (2.2) upwards on the
rod (2.1).
2. Loosen the locking screw (2.6) and turn
the set point adjuster (2.3) clockwise ()
as far as it will go to close the restriction
(2.7). Close the restriction (2.7).
3. Determine the turns required to achieve
the desired ow rate from the adjustment
diagrams (see Table 7-2).
4. Turn the set point adjuster (2.3) counter-
clockwise () by the corresponding num-
ber of turns.
5. Thread the lock nut (2.2) clockwise ()
as far as it will go onto the rod (2.1). The
restriction opens until the adjusted set
point is reached.
6. Check the ow rate and correct it, if nec-
essary. Secure this setting with the lock-
ing screw (2.6).
7. Retract the actuator stem (1.1) using the
manual override. Place the actuator on
the restriction connection. Secure it by
tightening the hex nut (1.3, see 'Tighten-
ing torques' in Annex).
8. Extend the actuator stem all the way to
the rod (2.1) using the manual override.
9. Position the stem connector (1.2) and fas-
ten with screws.
1)
Alternatively: Type5825
2)
Alternatively: Type5824-30