EB 8384-4 EN 69
Start-up and settings
Turn Pin position on lever (see relevant
section on attachment)
Press .
Turn
Code 5
Press
, Code 5 blinks.
Turn
Nominal travel of the valve
Press
.
Select the initialization mode:
Init mode
Default MAX
Turn Code 6
Press
, Code 6 blinks.
Turn
NOM
Press
to conrm the NOM as the initial-
ization mode.
Start initialization:
Î Press INIT key.
Î After initialization, check the direction of
action (Code7) and, if necessary,
change it.
7.6.3 MAN – Initialization
based on a manually
selected range
Before starting initialization, move the con-
trol valve manually to the OPEN position.
Turn the rotary pushbutton (
) clockwise in
small steps. The valve must be moved with a
monotonically increasing signal pressure.
The positioner calculates the differential trav-
el/angle from the OPEN and CLOSED posi-
tions and adopts it as the operating range
with limits of lower travel/angle range value
(Code8) and upper travel/angle range val-
ue (Code9).
Enable conguration:
If no settings are entered within 120 sec-
onds, the enabled conguration function be-
comes invalid.
Enable conguration
Default: No
Turn g Code 3, display: No
Press
, Code 3 blinks.
Turn
YES
Press
, display:
Enter the pin position:
mm
Pin position
Default: No
Turn Code 4
Press
, Code 4 blinks.
Turn
Pin position on lever (see relevant
section on attachment)
Press .
Note