76 EB 8384-4 EN
Operation
8 Operation
Risk of injury due to the actuator stem ex-
tending or retracting.
Do not touch or block the actuator stem.
8.1 Enabling and selecting pa-
rameters
All codes and their meaning and default set-
tings are listed in the code list in section14.
Codes which are marked with an asterisk
must be enabled with Code3 before the as-
sociated parameters can be congured as
described below.
Code3
Conguration not enabled
Conguration enabled
Turn g Code 3, display: No
Press
, Code 3 blinks.
Change the setting in Code3.
Turn YES
Press
, display:
Conguration is enabled.
You can now congure codes one after the
other:
Turn to select the required code.
Press to activate the selected code. The
code number starts to blink.
Turn to select the setting.
Press
to conrm the selected setting.
If no settings are entered within 120sec-
onds, the enabled conguration function be-
comes invalid and the display returns to
Code0.
Cancel the setting:
Canceling the reading
To cancel a value before it is conrmed (by
pressing
) proceed as follows:
Turn
g ESC
Press
.
The entered value is not adopted.
8.2 Operating modes
8.2.1 Automatic and manual
modes
After initialization has been completed suc-
cessfully, the positioner is in
automatic
mode (AUTO).
WARNING
!
Note