76 EB 8384-4 EN
Operation
8 Operation
Risk of injury due to the actuator stem ex-
tending or retracting.
Do not touch or block the actuator stem.
8.1 Enabling and selecting pa-
rameters
All codes and their meaning and default set-
tings are listed in the code list in section14.
Codes which are marked with an asterisk
must be enabled with Code3 before the as-
sociated parameters can be congured as
described below.
Code3
Conguration not enabled
Conguration enabled
Turn g Code 3, display: No
Press
, Code 3 blinks.
Change the setting in Code3.
Turn YES
Press
, display:
Conguration is enabled.
You can now congure codes one after the
other:
Turn to select the required code.
Press to activate the selected code. The
code number starts to blink.
Turn to select the setting.
Press
to conrm the selected setting.
If no settings are entered within 120sec-
onds, the enabled conguration function be-
comes invalid and the display returns to
Code0.
Cancel the setting:
Canceling the reading
To cancel a value before it is conrmed (by
pressing
) proceed as follows:
Turn
g ESC
Press
.
The entered value is not adopted.
8.2 Operating modes
8.2.1 Automatic and manual
modes
After initialization has been completed suc-
cessfully, the positioner is in
automatic
mode (AUTO).
WARNING
!