EasyManua.ls Logo

Samson 3730-4 - Fail-Safe Position (SAFE)

Samson 3730-4
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EB 8384-4 EN 77
Operation
%
Automatic mode
Switching to manual mode (MAN)
Turn Code 0
Press
, display: AUtO, Code 0 blinks.
Turn
MAN
Press
. The positioner changes to the man-
ual mode (
).
The manual mode starts using the last set
point of the automatic mode, ensuring a
bumpless changeover. The current position is
displayed in %.
Adjust the manual set point
% %
Turn Code 1
Press
, Code 1 blinks.
Turn
until sufcient pressure has been
built up in the positioner and the control
valve moves to the required position.
The positioner automatically returns to
Code0 if no settings are made within
120seconds, but remains in the manual
mode.
Switch to
automatic mode
Turn
Code 0
Press
, Code 0 blinks.
Turn
AUtO
Press
. The positioner switches to automat-
ic mode.
8.2.2 Fail-safe position (SAFE)
If you want to move the valve to the fail-safe
position determined during start-up (see sec-
tion7.1), proceed as follows:
Turn Code 0
Press
, display: current operating mode
(AUTO or MAN), Code0 blinks.
Turn SAFE
Press
, display: S
The valve moves to the fail-safe position.
If the positioner has been initialized, the cur-
rent valve position in % is indicated on the
display.
Note