40 EB 8384-4 EN
Attachment to the control valve – Mounting parts and accessories
4.7 Attachment of external po-
sition sensor
Positioner unit with sensor mounted on a mi-
cro-ow valve
− Required mounting parts and accessories:
Table7 on page52
In the positioner version with an external po-
sition sensor, the sensor located in a separate
housing is attached over a plate or bracket to
the control valve. The travel pick-off corre-
sponds to that of a standard device.
The positioner can be mounted as required to
a wall or a pipe.
For the pneumatic connection either a con-
necting plate (6) or a pressure gauge bracket
(7) must be xed to the housing, depending
on the accessory chosen. Make sure the seals
(6.1) are correctly inserted (see Fig.5, bot-
tom right).
For the electrical connection a 10meter con-
necting lead with M12x1 connectors is in-
cluded in the scope of delivery.
− In addition, the instructions in sections5.1
and 5.2 apply for the pneumatic and elec-
trical connection.
Operation and setting are described in
sections7 and 8.
− Since 2009, the back of the position sen-
sor (20) is tted with two pins acting as
mechanical stops for the lever (1). If this
position sensor is mounted using old
mounting parts, two corresponding
Ø8mm holes must be drilled into the
mounting plate/bracket (21). A template is
available for this purpose. See Table7.
Note