74 EB 8384-4 EN
Start-up and settings
Turn ZP
Î Press INIT key.
Zero calibration starts. The positioner
moves the valve to the CLOSED position
and recalibrates the internal electrical
zero point.
7.8 Reset to default settings
This function resets all start-up parameters as
well as the diagnosis to the factory default
settings (see code list in section 14).
Enable conguration:
Turn
g Code 3, display: No
Press
, Code 3 blinks.
Turn
YES
Press
, display:
Reset start-up parameters:
Reset
Default: No
Turn g Code 36, display: ••–••–
Press
, Code 36 blinks.
Turn
Std
Press
.
All start-up parameters as well as the diag-
nosis are reset to their default values.
Code 36 - diAG allows just the diagnosis
data (EXPERTplus) to be reset. Refer to the
Operating Instructions for EXPERTplus
valve diagnostics u EB8389.
The FACTORY_RESET parameter resets the
control and identication parameters as
well as the bus address. Refer to Congu-
ration Manual uKH8384-4.
7.9 Start-up via local interface
(SSP)
The positioner can either be start up, cong-
ured, and operated on site, using the eld-
bus conguration or operating system, or
TROVIS-VIEW operator interface connected
over the serial interface in the positioner. Use
the TROVIS-VIEW software with 3730-4 de-
vice module installed.
To connect the positioner directly to the com-
puter via the local serial interface, an adapt-
er (order no. 1400-7700) is required.
The power supply for the positioner can be
supplied either over the connection to the
eldbus segment or over a DC voltage
source (9 to 32V) connected to the bus ter-
minals in the positioner (a suitable intrinsi-
cally safe source must be used inside and
outside the hazardous area for intrinsically
safe positioners). The simultaneous operation
of TROVIS-VIEW and the eldbus system is
possible without any restrictions when con-
nected to a PROFIBUS-PA segment.
7.10 Setting the bus address
A maximum of 32 positioners in a safe
(non-hazardous) area can be operated in
parallel over a segment coupler in one PRO-
FIBUS-PA segment. Each positioner connect-
ed in the segment must be assigned a unique
bus address between 0 and 125.