EasyManua.ls Logo

Samson 3730-4 - Initialization

Samson 3730-4
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EB 8384-4 EN 81
Adjusting the limit switch
The required switching function, i.e. whether
the output relay is to be picked up or re-
leased when the tag enters the eld, must be
selected at the switching amplier, if re-
quired.
Adjusting the switching point:
During adjustment or testing, the switching
point must always be approached from
mid-position (50%).
To guarantee the switching under all ambient
conditions, adjust the switching point ap-
prox. 5% before the mechanical stop (OPEN
– CLOSED).
For CLOSED position:
1. Initialize the positioner.
2. Move the valve to 5% in the MAN mode
(see display).
3. Adjust the tag at the yellow adjustment
screw (2) until the tag enters or leaves
the eld and the switching amplier re-
sponds.
You can measure the switching voltage
as an indicator.
Contact function:
Tag leaving the eld > contact is closed.
Tag entering the eld > contact is
opened.
For OPEN position:
1. Initialize the positioner.
2. Move the valve to 95% in the MAN
mode (see display).
3. Adjust the tag (1) at the yellow adjust-
ment screw (2) until the tag enters or
leaves the eld of the proximity switch
(3).
You can measure the switching voltage
as an indicator.
Contact function:
Tag leaving the eld > contact is closed.
Tag entering the eld > contact is
opened.
9.1 Retrotting an inductive
limit switch
Required retrot kit:
Limit switch Order no. 1400-7460
The same requirements apply to retrotting
an inductive limit switch as to servicing the
positioner. For explosion-protected position-
ers, the requirements in section11 „Servic-
ing explosion-protected devices“ need to be
kept. Check the "Limit switch, inductive" box
on the nameplate after installing the limit
switch.