EB 8384-4 EN 71
Start-up and settings
Enable conguration
Default: No
Turn g Code 3, display: No
Press
, Code 3 blinks.
Turn
YES
Press
, display:
Enter the pin position and nominal range:
mm
Pin position
Default: No
mm
Nominal range
(locked when Code4 = No)
Turn Code 4
Press
, Code 4 blinks.
Turn
Pin position on lever (see relevant
section on attachment)
Press .
Turn
Code 5
Press
, Code 5 blinks.
Turn
Nominal travel of the valve
Press
.
Select the initialization mode:
Init mode
Default MAX
Turn Code 6
Press
.
Turn
SUb
Press
to conrm the SUb as the initializa-
tion mode.
Enter the direction of action:
Direction of action
Default
Turn Code 7
Press
, Code 7 blinks.
Turn
Direction of action (ää/äæ)
Press
.
Deactivate travel limit:
Travel limitation
Default: No
Turn Code 11
Press
, Code 11 blinks.
Turn
g No
Press
.