press 10 seconds
The address is
adopted straightaway, provided that cyclic
data exchange is not taking place.
During the cyclic data exchange, the newly
set address for the positioner is saved and
adopted after the cyclic data exchange is
finished.
The newly assigned address is indicated un
-
der Code 46 in alternating sequence with
the current address. The new address is
marked with “n“ (new) and the currently
used address with “o“ (old).
Note: The bus address can only be imple
-
mented by the PROFIBUS command
SET_ADRESS when the bus address is set to
the default setting [126].
EB 8384-4 EN 73
Start-up and settings