After enabling:
Default OFF
Turn
→
Code 36, press ,
turn
→
RUN, press .
All control parameters are reset and can be
reconfigured.
Note: Reset the control and identification
parameters as well as the bus address with
the FACTORY_RESET parameter (see page
134).
5.10 Start-up via local interface
(SSP)
The positioner can either be commissioned,
configured, and operated on site, using the
Fieldbus configuration or operating system,
or TROVIS-VIEW operator interface con
-
nected over the serial interface in the
positioner.
Use the TROVIS-VIEW software with 3730-4
device module installed.
To connect the positioner directly to the PC
via the local serial interface, an adapter (or
-
der no. 1400-7700) is required.
The positioner can be supplied with power
by connecting it either to a fieldbus segment
or over a DC voltage source (9 to 32 V)
connected to the bus terminals in the
positioner. A suitable intrisically safe source
mut be used within the hazardous area and
the safe area when an intrinsically safe
positioner is used.
The simultaneous operation of
TROVIS-VIEW and the fieldbus system is
possible without any restrictions when con
-
nected to a PROFIBUS-PA segment.
5.11 Setting the bus address
A maximum of 32 positioners in a safe
(non-hazardous) area can be operated over
a segment coupler in one PROFIBUS-PA seg
-
ment.
Each positioner connected in the segment
must be assigned a unique bus address be-
tween 0 and 125.
Enable configuration:
Default OFF
Turn
→
Code 3, press ,
turn
→
ON, press .
After enabling:
Default 126
Turn
→
Code 46, press ,
turn
→
required address,
72 EB 8384-4 EN
Start-up and settings