The table below containing the condensed
state is reached from the summary of active
alarms.
Status modification
The classification of the status alarms can be
assigned as required using the
TROVIS-VIEW software connected to the lo
-
cal SSP interface of the positioner or over
the PA parameters.
CAUTION
All extended alarms issued by the EXPERT
+
diagnostics are assigned the “No message”
status.
Logging and displaying diagnostic
functions/alarms
The last 30 alarms are logged in the
positioner. An alarm that is repeated is only
logged when it first occurs.
The alarms and the condensed state appear
on the display as described in the code list
(section 15.1). In addition, the diagnostic
parameters are available over the communi
-
cation interface of the positioner.
The diagnostic functions can easily be dis
-
played and configured using the
TROVIS-VIEW software connected over the
local interface (SSP) or over PROFIBUS.
76 EB 8384-4 EN
Status and diagnostic alarms
Status alarm
Engineering tool/
TROVIS-VIEW (version 3.40 and higher)
Positioner display
No message, ok green
Function check orange
tEsting, tunE or tEst
Maintenance required
Maintenance demanded
blue
Process related fault
Out of specification
Maintenance alarm red
Condensed state