Switching output Y2 as break and make contact
Y2C
0
— Break (NO) contact
1
— Make (NC) contact
Adaption
(self-tuning)
AdP
0
— Off, no adaption
1
— Ready for adaption, optimize following disturbance z
Adaption is an auto-tuning function implemented in the start-up phase
which allows the controller to independently adapt (tune) itself to the condi-
tions of the controlled system and calculate the optimum control par-
ameters. For those controlled systems which are critical and extremely fast,
those in which the control valve is not adjusted abruptively, configuration
block is to be set to
AdP
=
0
and, hence, disabled (see also section 6.3).
Enter code numbers
CPA
and
CCO
Code numbers
CPA
and
CCO
CPA
— Code number of the parameterization level
CCO
— Code number of the configuration level
Range of values
0 to 9999
Procedure for entering/modifying the code number:
Press yellow
ENTER
key (8);
PA
appears in the bottom display.
Press
cursor
key (5) ;
CO
appears in the bottom display.
Press
ENTER
key (8);
CO
display flashes. Default code number
0
is dis-
played in the top display panel.
If a code number has already been defined, enter this number using
cursor
keys (5) and (subsequent modification is then possible).
Press
ENTER
key (8)—.
The configuration level is opened
and the first con-
figuration block
In
is displayed.
Actuate
cursor
keys (5) and until either configuration block
CPA
ap-
pears for the parameterization level or configuration block
CCO
appears
for the configuration level.
Press
ENTER
key (8)—.
CPA
or
CCO
, resp. flash.
0
or the previously entered
code number appear in the top display.
Use the
cursor
keys (5) and to enter or modify the desired code num-
ber.
Press
ENTER
key (8) in order to accept and store the personal
code number
Actuate
operating
key (7) in order to return the controller to the operating
level (standard operation)
22