Checklist:
Device: Plant: Process designation: Date:
Selection
option/
block
Designation Range of values Factory
default
Start-up
values/
modifications
Operating level:
X
Controlled variable Dep. on input —
W1
Internal setpoint 1 In__ to In
—
0
XD
Control deviation (error) –100.0 to 100.0 % —
Y
Output variable Y__ to Y
—
—
W2
Internal setpoint 2 In__ to In
—
0
Parameterization level:
P
Proportional-action coefficient Kp 0.1 to 100.0 1.0
I
Integral (reset) time Tn 0 = Off 0 to 2000 s 0
d
Derivative (rate) time Tv 0 = Off 0 to 2000 s 0
dP
Derivative (rate) gain 0 = Off 0.0 to 10.0 0.0
Y__
Min. output variable limit –110.0 to Y
—
% 0.0
Y
—
Max. output variable limit Y__ to 110.0 % 100.0
YP
Working point –110.0 to 110.0 % 0.0
1A
Limit value Y1 Acc. to alarm cond. 0.0
1H
Differential gap Y1 0.1 to 100.0 % 1.0
2A
Limit value Y2 Acc. to alarm cond. 0.0
2H
Differential gap Y2 0.1 to 100.0 % 1.0
t1
Period 1 to 9999 s 120
Motor operating time 1 to 9999 s 120
td
Dead band (Y = 1) 0.1 to 100.0 % 1.0
Min. pulse duration 0.1 to 100.0 % 2.0
tH
Hysteresis 0.1 to 100.0 % 1.0
34