Refrigerant pipe installation
f Example of refrigerant calculation for HP models
Classication Size of liquid pipe
Length (m)
Unit amount of
refrigerant (kg/m)
Amount of
additional
refrigerant (kg)
Total amount
of additional
refrigerant (kg)
①②× ∑(×)
Liquid pipe ()
Ø 6.35 35 0.02 0.7
5.575
Ø 9.52 50 0.06 3.0
Ø 12.70 15 0.125 1.875
Classication
Model name of
indoor unit
Number of units
Unit amount of
refrigerant (kg/EA)
Amount of
additional
refrigerant (kg)
Total amount
of additional
refrigerant (kg)
①②× ∑(×)
Indoor unit ()
4way cassette
(AM071FN4DEH)
40.451.80
3.10
Slim duct
(AM056FNLDEH)
20.350.70
Slim duct
(AM045FNLDEH)
10.350.35
1way cassette
(AM036FN1DEH)
10.250.25
- Total amount of refrigerant (+) = 5.575+3.10 = 8.675 (kg)
f Example of refrigerant calculation for HR models
Classication Size of liquid pipe
Length (m)
Unit amount of
refrigerant (kg/m)
Amount of
additional
refrigerant (kg)
Total amount
of additional
refrigerant (kg)
①②× ∑(×)
Liquid pipe ()
Ø 6.35 15 0.02 0.3
11.965
Ø 9.52 112 0.06 6.72
Ø 12.70 25 0.125 3.125
Ø 15.88 10 0.18 1.8
Ø 6.35
(EEV Kit ~ indoor unit)
20.010.02