Insulating the pipe located inside of the outdoor unit
f With a pipe insulator, insulate the pipe up to whole service valve located inside of the outdoor unit.
f Seal the gap between the outdoor unit pipe and the insulator. Rainwater and dewdrops may soak through the gap
between the pipe and the insulation of the outdoor unit installed on the outside.
f Separate the cover of the pipe and close it after insulation work. Only remove a knock-out hole cover where the pipe will
be installed. If the knock-out hole is open unnecessarily, it must be closed. If not, small animals such as squirrels and rats
may get into the unit through the hole and the unit may be damaged.
H/P
H/R
Charging refrigerant (for the turkish market only)
f The R410A refrigerant is blended refrigerant. Add only liquid refrigerant.
f Measure the quantity of the refrigerant according to the length of the liquid side pipe. Add quantity of the refrigerant
using a scale.
Important information regulation regarding the refrigerant used
This product contains uorinated greenhouse gases. Do not vent gases into the atmosphere.
Inform user if system contains 5 tCO
2
e or more of uorinated greenhouse gases. In this case, it has to be checked
for leakage at least once every 12 months, according to regulation n°517/2014. This activity has to be covered
by qualied personnel only. In case situation above (5 tCO
2
e or more of R-410A), installer (or recognized person
which has responsibility for nal check) has to provide a maintenance book, with all the information recorded
according to REGULATION (EU) No 517/2014 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 April
2014 on uorinated greenhouse gases.
CAUTION

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung DVM S Series and is the answer not in the manual?

Samsung DVM S Series Specifications

General IconGeneral
RefrigerantR410A
Operating Temperature Range (Cooling)-5°C to 48°C
Piping Length (Total)1000m
Inverter TechnologyYes
TypeVRF System
Compressor TypeInverter Scroll Compressor
Energy EfficiencyHigh Efficiency
ControlCentralized Control, Individual Control
Indoor Unit OptionsCassette, Duct, Wall Mount, Ceiling