2nd Edition of TEMP2000_Series IM : July. 16. 2010 Page 19 / 87
1.3.3.3 RELAY Wiring
Make sure POWER OFF before wiring DO REALY.
RELAY rating : Normal Open 30VDC 1A max, 250VAC 1A max.
30V DC 1A Max, 250V AC 1A Max 30V DC 1A Max, 250V AC 1A Max
NO(NORMAL OPEN):30V DC 3A Max, 250V AC 3A Max
NC(NORMAL CLOSE):30V DC 0.5A Max, 250V AC 1A Max
NO(NORMAL OPEN):30V DC 3A Max, 250V AC 3A Max
NC(NORMAL CLOSE):30V DC 0.5A Max, 250V AC 1A Max
1.3.3.4 Digital Input wiring
Use a mechanical contactor (non-voltage type) as relay for the digital input (DI).
The relay for DI must have sufficient on-off repeatability at 5V open voltage and 1 mA short circuit
current.
The OPEN COLLECTOR for DI should have low ON state voltage (<2V) and low leakage current less than
100μA at OFF state.
RELAY DI TRANSISTOR DI
I/O1 BOARD
I/O2 BOARD
RLY1
COM
RLY2
COM
RLY13
COM
RLY14
COM
I/O1 BOARD
I/O1 BOARD
RLY9_NC
RLY9_NO
COM
RLY10_NC
RLY10_NO
RLY11_NC
RLY11_NO
COM
RLY12_NC
RLY12_NO
I/O1 BOARD
I/O1 BOARD
DI1
DI2
DI16
DI_COM
DI1
DI2
DI16
DI_COM

Other manuals for Samwontech TEMP2500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samwontech TEMP2500 and is the answer not in the manual?

Samwontech TEMP2500 Specifications

General IconGeneral
BrandSamwontech
ModelTEMP2500
CategoryController
LanguageEnglish

Related product manuals