EasyManuals Logo

Satec PM135P User Manual

Satec PM135P
167 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #144 background imageLoading...
Page #144 background image
Appendix A Technical Specifications
144 PM135 Powermeter Series
Solid State relay option (4DI/2DO only)
2 relays rated at 0.15A/250 V AC/DC, 1 contact (SPST Form A)
Galvanic isolation: 3750 VAC 1 min
Operate time: 1 ms max.
Release time: 0.25 ms max.
Update time: 1 cycle
Connector type: removable, 4 pins.
Wire size: 14 AWG (up to 1.5 mm2)
A.6 Optional Digital Inputs
4, 8 or 12 Digital Inputs (4DI/2DO, 8DI or 12DI/4DO Optional module)
Dry Contacts, internally wetted @ 24VDC
Wet contact @ 250VDC (12DI/4DO only)
Sensitivity: Open @ input resistance >100 k
, Closed @ Input
resistance < 100
Galvanic isolation: 3750 VAC 1 min
Internal power supply: 24VDC
Scan time: 1 ms
Connector type: removable, 5 pins.
Wire size: 14 AWG (up to 1.5 mm2)
A.7 Optional Analog Outputs
4 Analog Outputs optically isolated (AO Optional module)
Ranges (upon order):
1 mA, maximum load 5 k
(100% overload)
0-20 mA, maximum load 510
4-20 mA, maximum load 510
0-1 mA, maximum load 5 k
(100% overload)
Isolation: 2500 VAC 1 min
Power supply: internal
Accuracy: 0.5% FS
Update time: 1 cycle
Connector type: removable, 5 pins.
Wire size: 14 AWG (up to 1.5 mm2)
A.8 Communication Ports
COM1
RS-485 optically isolated port
Isolation: 3000 VAC 1 min
Baud rate: up to 115.2 kbps.
Supported protocols: MODBUS RTU, DNP3, SATEC ASCII, IEC 60870-5-101