Transport and Installation
WP33L_BA_K1_12_en_08.fm
35
– At a room temperature below +5°C, the room needs to be
heated.
– Choose the location such that the Sauer compressor is acces-
sible and has sufficient clearance all round (see installation
documents).
– The installation must ensure that the cooling fan cannot recir-
culate the warm cooling air.
– Do not install several compressors one after the other, to pre-
vent one compressor from taking in the warmed-up cooling air
of another compressor.
Note!
The air temperature at the cooling air intake to the compressor
must not exceed +55°C when the compressor is running. Room
conditions and the heat generated by the compressor and other
machines installed in the room, must be taken into considerati-
on.
• If necessary, install a ventilation or extraction system at the in-
stallation.
• Install the fresh air feed in such way that the cooling air stream
is never directed at the compressor. This helps to avoid any
risk of condensation inside the compressor and subsequent
damage.
Note!
J.P. SAUER & SOHN would be pleased to advise on the instal-
lation of the compressors.