EasyManua.ls Logo

Schwank S100 - Page 27

Schwank S100
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
27
S100-F / ITB-F I&O Manual
IM101230
RD: JAN 2014
RL: 9A
HORIZONTAL VENT THROUGH THE SIDEWALL:
 Any horizontal portion of the flue vent system must slope downwards approximately 1/4"
per foot (63 mm/ 300 mm) toward the vent terminal - radiant tube must be level.
continued ……..
common thermostat or “ON/OFF” switch must control the two commonly vented heaters.
 Install a minimum 36 inch (91 cm) length of minimum 26 gauge single walled 4” (10 cm) di-
ameter vent pipe on the system, and a minimum 12 inch (30 cm) before any Tee or Elbow.
 Seal all vent connections with high temperature sealant. Vent connections must be secured
with three (3) #8 sheet metal screws uniformly spaced around the circumference of the pipe.
 Any horizontal vent pipe must slope approx. 1/4” per foot away from heater
 When the vent pipe passes through a cold or unheated area where the ambient temperature
is likely to produce condensation of the flue gases, the vent pipe will be insulated with a suit-
able material as approved and specified by the insulation manufacturer to withstand tem-
perature up to 460°F (238°C).
 The vent system must always be adequately supported to prevent sagging.
FIGURE 20 - Heater Expansion - Suggested Vent Configuration*
* Other means of slip
fit installation of the
vent and duct are ac-
ceptable providing
there is adequate al-
lowance for free ex-
pansion and contrac-
tion of the system,
and free flow of vent
gases and combus-
tion air.
FIGURE 21 - Horizontal Vent - ALL vent pipe and adapters by others
Clearances apply to JA-0528-XX 4” (10 cm) or JA-0529-XX 6” (15 cm) Vent Terminals
See notes below for use of other approved vent terminations
Clearances

Table of Contents

Related product manuals