EasyManua.ls Logo

Secure Care KinderGUARD ID - Delayed Egress and Fire Alarm Connections; Figure 9-11 Push Button and Remote Keypad Interface

Default Icon
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Doc. No.: A05280692 Rev. AE ECO: 13200 Date: 11/04/2019
36
Figure 9-12 Push Button and Remote Keypad Interface
Delayed Egress and Fire Alarm Connections
Each of our panels has a delayed egress connection and a fire alarm connection per Life Safety Code 101 and
NFPA code 101. The fire alarm panel connection is designed to disengage the magnetic lock in the event of a
fire alarm. The delayed egress connection will sense when pressure is applied to the door, releasing the
magnetic lock 15 seconds later. Connect the red wire from your fire alarm relay (dry contact) to the positive
reference termination on the panel; connect the black wire from your fire alarm relay (dry contact) to the
negative reference termination on the panel. When connecting the delayed egress (1), simply connect both
leads from the lock to the panel. Polarity does not matter. Connections are shown in Fig. 9-12.
WARNING: Fire input + and – is only a reference. No voltage is to be
applied to the fire inputs, they are dry inputs only. Applying power to the
SECTION 9 INSTALLATION AND CONNECTIONS

Table of Contents