Doc. No.: A05280692 Rev. AE ECO: 13200 Date: 11/04/2019
Setting Exit Panel ID Code
Each ID Exit Panel requires its own unique ID code for reporting purposes on the CAN bus (if used). An event message
will then be transmitted on the CAN bus beginning with the Exit Panel ID code followed by the message string. The Exit
Panel ID is also supervised by the XIU for power. Only ID’s 001-095 are valid ID codes.
Panel ID Code Factory Default 255
To change the panel ID code, follow the three listed steps without pausing for greater than one second between
keystrokes.
1. Enter *567 or currently programmed secondary code
2. Enter *9876543213#XXX (XXX = three digit number)
Two confirmation beeps = change accepted
Single confirmation beep = change declined
To view the panel ID code, follow the three listed steps without pausing for greater than one second between
keystrokes.
1. Enter *567 or currently programmed secondary code
2. Enter *9876543213#999. The ID Code will be given in three series of blinks (# of beeps for number in the
code, i.e. one beep = 1, etc… ten beeps = 0) separated by pauses.
Escort Pendant Enable/Disable
The Escort Pendant was designed to allow facility staff members to be able to put the Secure Care Products ID Exit Panel
into an escort mode without having to manually enter an authorized escort/reset code at the Exit Panel keypad. This
allows for easier travel and movement of staff with residents or infants throughout the facility and covered (protected)
areas.
To Enable Escort Pendant Feature: Factory Default Disabled
1. Enter *567*9876543215#998
4 beeps=accepted
To Disable Escort Pendant Feature:
1. Enter *567*9876543215#908
3 beeps=accepted
Defaulting The STAT ID Panel
Resetting the exit panel back to factory default will reset all of the programmed information inside the panel.
To reset the panel to factory settings: Enter *309 *9876543214
SECTION 10 PROGRAMMING INSTRUCTIONS