Doc. No.: A05280692 Rev. AE ECO: 13200 Date: 11/04/2019
No Code/ Irreversible Delayed Egress
Each Exit Panel controlling an electromagnetic lock has a required time period for pressure applied to a door to
release the locking feature as required by NFPA 101. Refer to the NFPA 101 Life Safety Code or your local
fire Marshall/safety inspector for guidance on local requirements. This feature, when enabled, will continue
with the delayed egress after the activation time is passed. No Code will stop or reset the delayed egress until
the door is opened and then closed. At this time you can reset the delayed egress.
No Code/ Irreversible Delayed Egress Factory Default Disabled
To enable the No Code/ Irreversible delayed egress feature, follow the three listed steps without pausing for
greater than one second between keystrokes.
1. Enter *567 or the currently programmed secondary code
2. Enter *9876543217#666
3. Three confirmation beeps or blinks = change accepted
To disable the No Code/ Irreversible delayed egress feature, follow the three listed steps without pausing for
greater than one second between keystrokes.
1. Enter *567 or the currently programmed secondary code
2. Enter *9876543217#606
3. One beep/blink confirmation = change accepted
Fire Alarm Input Selection
Fire Alarm Input Factory Default Normally Open
To change the fire alarm input between normally open and normally closed:
Normally Open fire alarm contact active (looking for a closure from the Fire Alarm Relay to unlock doors)
1. Enter *567 or currently programmed secondary code
2. Enter *9876543216#000
Two confirmation beeps = change accepted
One confirmation beep = change not accepted
Normally Closed fire alarm contact active (looking for an open from the Fire Alarm relay to unlock the doors)
1. Enter *567 or currently programmed secondary code
2. Enter *9876543216#001
Three confirmation beeps = change accepted
One confirmation beep = change not accepted
Enable/Disable the Signal LED
This command will disable the yellow transmitter detected indicator on the exit panel. This may help prevent wearers of
the motion detect transmitters from watching the indicator and then attempting to exit the door.
To Enable or Disable the Signal LED on the ID Exit Panel Factory Default LED Enabled
1. Enter *567*6 and hold the 6
2. 2 Beeps – Signal LED disabled
3. 1 Beep – Signal LED enabled
SECTION 10 PROGRAMMING INSTRUCTIONS