Doc. No.: A05280692 Rev. AE ECO: 13200 Date: 11/04/2019
Three confirmation beeps = Change Accepted
Escort Time
Each ID Exit Panel has a time period that allows passing through a door without creating an alarm. The factory default
escort time is thirty (30) seconds.
Escort Time Factory Default 30 Seconds
To change the escort time, follow the three listed steps without pausing for greater than one second between
keystrokes.
1. Enter *567 or currently programmed secondary code
2. Enter *9876543215#
3. Enter new three digit time in seconds (up to a maximum of 900 seconds but not less then 15 seconds)
Example: 60 seconds = 060, 90 seconds = 090, 120 seconds = 120
Two confirmation beeps = Change Accepted;
One confirmation beep = Change Not Accepted
Delayed Egress Release Time
Each ID Exit Panel controlling an electromagnetic lock has a required time period for pressure applied to a door to
release the locking feature as required by NFPA 101. Refer to the NFPA 101 Life Safety Code or your local Fire
Marshall/Safety Inspector for guidance on local requirements.
Delayed Egress Release Time Factory Default 15 Seconds
To change the release time from 15 to 30 seconds, follow the three listed steps without pausing for greater
than one second between keystrokes.
1. Enter *567 or currently programmed secondary code
2. Enter *9876543217#030
Multiple confirmation beeps = change accepted
One confirmation beep = change not accepted
To change the release time from 30 to 15 seconds, follow the three listed steps without pausing for greater
than one second between keystrokes.
1. Enter *567 or currently programmed secondary code
2. Enter *9876543217#015
Multiple confirmation beeps = change accepted
One confirmation beep = change not accepted
SECTION 10 PROGRAMMING INSTRUCTIONS SECTION 10 PROGRAMMING INSTRUCTIONS