Loading...
Secutron Inc. 19
9. Write in the ‘standby’ time required. (24 or 60 Hr.)
10. Multiply the ‘standby’ Amps times the ‘standby’ time to get the ‘standby’ Amp-Hr. required.
11. Write in the ‘alarm’ time required in hours. (5 min. =.08 Hr.; 30 min. =0.5 Hr.)
12. Multiply the ‘alarm’ Amps times the ‘alarm’ time to get the ‘alarm’ Amp-Hr required.
13. Add the ‘standby’ Amp-Hr. to the ‘alarm’ Amp-Hr. for the total Amp-Hr. required.
14. Multiply the total Amp-Hr. times 1.20 for the minimum Amp-Hr. battery required to
support the system for the selected ‘standby time and the selected ‘alarm’ time.