6.1 Entering Installer Programming Mode
All zone alarms must be reset prior to entering the Installer Programming Mode. While the
panel is in Installer Programming Mode, the annunciators will show a trouble condition.
How to enter Installer Programming Mode
1. Remove the lower front cover and locate the ‘Walk Test Switch’ behind the control panel
PCB, as shown in Figure 17 Locating the Walk Test Switch.
2. Press and hold the Walk Test Switch for two seconds. The common trouble buzzer and
common trouble LED turn on and pulse ½ second on/off.
3. Press any button. The trouble buzzer is silent, and the zone 1 alarm LED turns on steady.
The common trouble LED continues to flash.
4. The panel is now ready to program.
Figure 17 Locating the Walk Test Switch